Site Accessibility Evaluation

Americans with Disabilities Act
Title II (Public Services: State and Local Government)
Evaluation PU19-000060 Cover Photo
Sandstone Park
4650 Pring Ranch Rd
Colorado Springs, CO 80922
Accessibility Evaluation
Inspection Date: 06/16/2022
Inspectors: Robert Hernandez
Prepared By
City of Colorado Springs Logo
City of Colorado Springs
(719) 385 - 5175
https://coloradosprings.gov/
Report Date: 03/04/2025

FOR RECORD:

FROM: Robert L. Hernandez, Title II ADA/Section 504 – Manager

DATE: 03/04/2025

SUBJECT: Sandstone Park Self-Evaluation

1. On 06/16/2022, Title II ADA / Section 504 Coordinator(s) from the Office of Accessibility performed a Title II - Americans with Disabilities Act (ADA) Self-Evaluation. This evaluation was performed in accordance with 1991/2010 ADA Standards for Accessible Design.

2. Priorities for removing barriers are assigned in accordance with the ADA Checklist for Existing Facilities, promulgated by the ADA National Network. The checklist follows the four priorities listed in the Department of Justice ADA Title III regulations. These priorities are equally applicable to state and local government facilities:

Priority 1 - Accessible approach and entrance
Priority 2 - Access to goods and services
Priority 3 - Access to public toilet rooms
Priority 4 - Access to other items such as water fountains and public telephones

3. Corrective actions to findings were / will be submitted to the City maintenance work request system and will be managed in accordance with the City Transition Plan. Note: Recommended corrections may be modified where appropriate. Corrections are developed in consideration of the “Program Access” provisions of Title II, where applicable.

4. A copy of this report will be maintained by the Office of Accessibility. Updates to the findings included in this report will be available at the following link: https://access6.bluedag.com/access/barriers/GfhHF91nlvMItTaD4rVzj85XBKNZxywJ. Alternatively, this link is available from the Office of Accessibility’s webpage on the City of Colorado Springs website.


City of Colorado Springs Title II ADA/Section 504 – Manager
30 S. Nevada Ave, Suite 301
Colorado Springs, CO 80903
ADACompliance@coloradosprings.gov


Atch 1. City of Colorado Springs, ADA Self-Evaluation Report

Sincerely,


Robert Hernandez

Findings

Exterior - Accessible Routes

BFID: 187941

There are multiple issues with this curb ramp including:

There are no detectable warnings.

There is 1-1/4" vertical displacement at the gutter pan.

There is 3/4" vertical displacement at the top of the ramp.

The ramp does not align with the ramp across Lasater Trail.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp, aligning it with the ramp across Lasater Trail.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Curb ramp was replaced.
Noncompliant curb ramp
Finding 187941 Corrected Photo

BFID: 194187

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Explore extending the ramp and moving the landing further up in order to achieve a compliant running slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 194188

Where there is a triangular junction of three routes, the "points" of that junction are turning spaces that shall not have slopes greater than 1:48 (2.08%). The "sides" of the triangle, connecting the paths that lead away from the junction to each other, are walking surfaces that shall not have running slopes greater than 1:20 (5%).

More than one of these elements have findings associated with them in this case.
Citation:
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace non-compliant turning spaces so that they have a less than 2% slope in all directions. Replace the connectors between these turning spaces so that they have cross slopes less than 2% and running slopes less than 5%.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 194188 Additional Photo

BFID: 194189

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 194190

Where there is a triangular junction of three routes, the "points" of that junction are turning spaces that shall not have slopes greater than 1:48 (2.08%). The "sides" of the triangle, connecting the paths that lead away from the junction to each other, are walking surfaces that shall not have running slopes greater than 1:20 (5%).

More than one of these elements have findings associated with them in this case.
Citation:
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace non-compliant turning spaces so that they have a less than 2% slope in all directions. Replace the connectors between these turning spaces so that they have cross slopes less than 2% and running slopes less than 5%.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 194190 Additional Photo
Finding 194190 Additional Photo
Finding 194190 Additional Photo
Finding 194190 Additional Photo

BFID: 194191

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 194191 Additional Photo

BFID: 194192

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 194192 Additional Photo
Finding 194192 Additional Photo
Finding 194192 Additional Photo

BFID: 194193

The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind to less than 1/2" bevel.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 194195

Where there is a triangular junction of three routes, the "points" of that junction are turning spaces that shall not have slopes greater than 1:48 (2.08%). The "sides" of the triangle, connecting the paths that lead away from the junction to each other, are walking surfaces that shall not have running slopes greater than 1:20 (5%).

More than one of these elements have findings associated with them in this case.
Citation:
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace non-compliant turning spaces so that they have a less than 2% slope in all directions. Replace the connectors between these turning spaces so that they have cross slopes less than 2% and running slopes less than 5%. It should be noted that the running slope issues on route section 2 cannot be rectified due to the existing terrain.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 194195 Additional Photo
Finding 194195 Additional Photo
Finding 194195 Additional Photo
Finding 194195 Additional Photo
Finding 194195 Additional Photo
Finding 194195 Additional Photo

BFID: 194196

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 194196 Additional Photo

BFID: 194197

Where there is a triangular junction of three routes, the "points" of that junction are turning spaces that shall not have slopes greater than 1:48 (2.08%). The "sides" of the triangle, connecting the paths that lead away from the junction to each other, are walking surfaces that shall not have running slopes greater than 1:20 (5%).

More than one of these elements have findings associated with them in this case.
Citation:
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace non-compliant turning spaces so that they have a less than 2% slope in all directions. Replace the connectors between these turning spaces so that they have cross slopes less than 2% and running slopes less than 5%.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 194197 Additional Photo
Finding 194197 Additional Photo
Finding 194197 Additional Photo
Finding 194197 Additional Photo
Finding 194197 Additional Photo

BFID: 194198

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace pads to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding